Fire Alarm Panel Battery Calculations
Please note that is calculator is for fire alarm systems and can be used with fire panels en54 power supply units and all other ancillary fire alarm equipment with 2 x 12v standby batteries wired in series.
Fire alarm panel battery calculations. C min i1 x t1 i2 x 1 25 definitions and example of the above i1 standby current from the fire alarm panel 0 05 amps t1 standby time assume category l1 24 hours i2 full alarm current from panel 0 3 amps. Fs tools expands on the previous ps tools platform and is required for programming the es 50x and es 200x panels. Es line of fire alarm control panels. Standby battery calculation the following formula can be used to calculate the appropriate standby battery size.
To calculate the battery size using the minimum code approach the quiescent and alarm loads must be tabulated and summed for all equipment devices and appliances connected to the power supply. Few ul listed panel manufacturers provide a sample calculation in which in alarm condition they recommend to consider only 5 or 20 of the detector to count. 2 zone 24v fire control 4 zone 24v fire cont comm 4 zone fire panel without mounting skirt lcd keypad for d7024 four zone expander d7024 8 relay board d7024 class a input adapter class b to a nac convertr alarm trouble relay module 8 led annunciator disp spv power supply addrss ckrt bstr fire comm pkg w d9112ltb d9124 accessory module carrier. Current draw must not exceed 1a aux output 2 non battery backed up.
Take the total standby current and multiply by 24 hours for standby take the total alarm current and multiply by 083 for 5 minutes or 249 for 15 minutes of alarm add the total of standby current x 24 to alarm current x 083 or 249 multiply the total of above by a safety factor of 1 2. Current draw must not exceed 1a and does not affect battery capacity total system load. This calculator assumes an alarm period of 30 minutes as stated in bs5839 1. Addressable panels battery calculators.
Hi guys i am confused regarding the battery calculation of fire alarm detection system. The standards state that in the event of a mains supply failure the backup batteries should be able to run the system for a minimum of 24hrs followed by 30minuites in full alarm condition all sounders running. Fs tools has been updated to include newly released products and makes it easier than ever before to program new features. All fire alarm systems must be fitted with a standby supply and this is achieved by using sealed lead acid sla batteries.